Ground Loop Isolator SEM1000 MKII

The SEM1000 MKII ground loop isolator is a DIN-rail mounted, loop-powered 4-20mA isolator built to eliminate ground loop interference in industrial process control circuits. Series-connected into a new or existing 4-20mA current loop, the SEM1000 MKII delivers a fully isolated 4-20mA output capable of driving up to 300 Ω load, with the output powered entirely from the input loop — no external power supply required.

Designed for reliability, the SEM1000 MKII requires no user adjustment during commissioning. Two front-panel accessible calibration potentiometers allow fine zero and span trimming when needed, and the unit is protected against incorrect loop connection provided rated currents and voltages are not exceeded. At just 12.5mm wide, it is one of the most compact ground loop isolators in its class, making it ideal for space-constrained control panels across oil & gas, water treatment, and general industrial process applications.

  • Ground Loop Elimination — Breaks ground loops between two process signal points, removing measurement noise and errors caused by differing earth potentials.
  • Loop-Powered Operation — Draws power entirely from the input current loop — no external power supply or wiring needed.
  • 300 Ω Output Drive — Delivers an isolated 4-20mA signal capable of driving into a 300 Ω maximum load.
  • No Commissioning Adjustment — Ships factory-calibrated; no user adjustment required during installation.
  • Front-Panel Calibration — Two accessible potentiometers allow minor zero and span trimming on site.
  • Compact 12.5mm DIN Rail Housing — Space-saving width for high-density control panel layouts.

What does the SEM1000 MKII ground loop isolator do?

It series-connects into a 4-20mA current loop and outputs an isolated, galvanically separated 4-20mA signal, eliminating ground loop interference between two points in a process control circuit.

Does the SEM1000 MKII need an external power supply?

No. The SEM1000 MKII is loop-powered, drawing the energy it needs directly from the input 4-20mA current loop.

What load can the SEM1000 MKII output drive?

The isolated output can drive into a maximum load of 300 Ω.

Does the SEM1000 MKII require calibration on installation?

No user adjustment is required during commissioning. Two front-panel potentiometers are available for minor zero and span trims if ever needed.